Phase Current based Fault Section Location for Single-Phase Grounding Fault in Non-Effectively Grounded Distribution Network
  • +5
  • zhongxue chang,
  • Nana Chang,
  • Wei Zhang,
  • Chenhao Zhang,
  • Guobing Song,
  • Jian Liu,
  • Zhihua Zhang,
  • Weibin Tan
zhongxue chang
Xi'an Jiaotong University

Corresponding Author:[email protected]

Author Profile
Nana Chang
Xi’an Jiaotong University
Author Profile
Wei Zhang
Xi'an Jiaotong University
Author Profile
Chenhao Zhang
Xi’an Jiaotong University
Author Profile
Guobing Song
Xi'an Jiaotong University School of Electrical Engineering
Author Profile
Jian Liu
State Grid Shaanxi Electric Power Company
Author Profile
Zhihua Zhang
Xi'an University of Technology
Author Profile
Weibin Tan
Zhuhai XJ Electric Co. Ltd
Author Profile

Abstract

Zero-sequence voltage and current based single-phase grounding (SPG) fault detection and location methods in non-effectively grounded distribution network have limitations in practical use due to lack of zero-sequence CT and PT in some cases. To deal with this problem, the phase current characteristics under SPG fault are analysed and the SPG fault detection method and section location method is proposed. PSCAD-based simulation results and fault recording data show that the proposed method behaves well when SPG fault with different impedances occurs in different sections. The proposed method can select the faulty phase automatically without using voltage signals, which is suitable for all IEDs.