Study on heat and moisture exchange characteristics of counter-flow wet
seawater shower cooling tower
Abstract
Cooling tower is an important part of circulating cooling water system.
This paper studies the counter-flow wet seawater shower cooling tower,
establishes and verifies the detailed thermal performance calculation
model. The influences of salinity, inlet velocity and droplet diameter
on cooling efficiency, heat dissipation, gas-phase thermal efficiency
and exergy efficiency were analyzed. The results showed that the cooling
efficiency, exergy efficiency, gas-phase thermal efficiency and heat
dissipation of the upper jet column were 15.59%, 4.89%, 8.62% and
34.58% higher than those of the lower jet column, respectively. With
the increase of droplet diameter, decreased by 38.76%, Q
decreased by 78.11%, decreased by 26.30% and decreased by 33.53%
under standard salinity conditions. Under high salinity conditions, is
reduced by 35.1%, is reduced by 17.16% and is reduced by 30.55%.With
the increase of air velocity, increased by 13.76%, Q increased
by 22.44%, decreased by 6.66%and decreased by less than 2% under the
standard salt condition.Under high salinity conditions, compared with
the standard salinity, the average reduction of is 2.96%, the average
reduction of is 1.63% and the average reduction of is 2.73%. Through
the optimization analysis of seawater cooling tower, it is obvious that
selecting the best operating conditions can improve the heat and
moisture exchange characteristics of seawater cooling tower.